The eGauge does not have a fixed BACnet register map. Instead, registers are mapped as they are created. Thus, the map for two different eGauges will differ based on the number of registers and the order they were added in. Registers are organized into groups, which are defined below:


Address Range
Group Description
Measured Value
0x20000
Group 1 - The RMS voltage of the voltage-taps can be read through this group.
Voltage [V]

0x30000
Group 2 - The RMS current measured by each CT can be read through this group.
Current [A]
0x50000
Group 3 - The frequency of the voltage-taps can be read through this group.
Line Frequency [Hz]
0x60000
Group 4 contains only the object ID 0x60000 and it reports the number of seconds since BACnet daemon startup. The daemon starts after enabling BACnet support through the UI or after power-cycling.
Timestamp [s]
0x70000
Group 5 reports the register value for each register (virtual and physical). The register values are time-weighted values and hence the unit of these object IDs is equal to the unit of the corresponding object ID in Group 6, multiplied by seconds. For example, for a register recording power, the Group 6 unit would be Watts, and therefore the Group 5 unit would be Watt-seconds (i.e., Joules).
REGVAL [various]
0x80000
Group 6 reports, for each virtual and physical register, the change in register value during the most recent one-second interval. For example, for a register recording power, the unit would be Watts, for a register recording voltage, the unit would be Volts.
REGCHG [various]

The BACnet PICS is available in the support knowledge base here.

Additional Tips:

  • Cumulative register values are found in Group 5, REGVAL. This provides time-weighted values such as kWh or amp-hours.
    • Cumulative register values may not start at zero. Thus, it is important to compare a previously received value with the current value to determine the total value change between two points in time.
  • Instantaneous (rate-of-change) register values are found in Group 6, REGCHG. These provide instantaneous values such as Watts or Amps.

  • The physical unit of this register depends on the quantity being recorded and can be obtained by reading the "unit" property (BACnet property 117) of the respective object id.
  • The register name for a given object ID can be obtained by reading the "name" property (BACnet property 77) from the object ID.

  • In Group 5 and 6, the first two object IDs will always be the Usage and Generation virtual registers. Any additional virtual registers come next. Physical registers are listed last.

  • The BACnet service is enabled on the eGauge through Settings -> BACnet.